Output
Output Power Capacity 2700 Watts / 3000 VA
Max Configurable Power 2700 Watts / 3000 VA
Nominal Output Voltage 120V
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
Crest Factor up to 5 : 1
Waveform Type Sine wave
Output Connections
(9) NEMA 5-15R
(2) NEMA 5-20R
Input
Nominal Input Voltage 120V
Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
NEMA L5-30P
Cord Length 2.44 meters
Input voltage range for main
operations
82 - 144V
Input voltage adjustable range for
mains operation
75 - 154V
Transfer Time 2-4 ms
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time 3 hour(s)
Replacement Battery APCRBC105
RBC™ Quantity 1
Typical Backup Time 15.0 minutes (1350 Watts)