APC SUA2200 User Manual Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 6
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
Output
Output Power Capacity 1980 Watts / 2200 VA
Max Configurable Power 1980 Watts / 2200 VA
Nominal Output Voltage 120V
Efficiency at Full Load 95%
Output Voltage Distortion Less than 5% at full load
Output Frequency (sync to mains) 47 - 53 Hz for 50 Hz nominal,57 - 63 Hz for 60 Hz nominal
Crest Factor up to 5 : 1
Waveform Type Sine wave
Output Connections
(8) NEMA 5-15R
(2) NEMA 5-20R
Input
Nominal Input Voltage 120V
Input Frequency 50/60 Hz +/- 3 Hz (auto sensing)
Input Connections
NEMA 5-20P
Cord Length 1.83 meters
Input voltage range for main
operations
82 - 144V
Input voltage adjustable range for
mains operation
75 - 154V
Batteries & Runtime
Battery Type Maintenance-free sealed Lead-Acid battery with suspended electrolyte : leakproof
Typical recharge time 3 hour(s)
Replacement Battery RBC55
RBC™ Quantity 1
Typical Backup Time
at Half Load
24.1 minutes (990 Watts)
Typical Backup Time
at Full Load
6.7 minutes (1980 Watts)
Runtime Chart Smart
-UPS