APC PM3 User Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 17
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
Parallel Connection
When making a parallel type of connection (Figure 2), the length of the wiring to the Surge Protection Device (SPD)
must be kept as short as possible to substantially enhance the performance. Long wire runs are to be avoided for the
unit to perform as intended.
To reduce the impedance the wire displays to surge currents, the phase, neutral (if used), and ground conductors are to
be routed within the same conduit and should be tightly bundled or twisted together to optimize performance of the
unit. Sharp bends in the conductors are to be avoided.
Wire Size
With a parallel connection, the size of the wiring to the SPD is independent of the ampere rating of the circuit to be
protected. The recommended wire size is based on the unit’s transient surge current capabilities. #6 AWG is the rec-
ommended wire size for phase, neutral, and ground.
**Surge Protection Devices are designed for use on the load side
of the service entrance disconnect only**
PM SERIES INSTALLATION INSTRUCTIONS
Typical Unit Installation - Three Phase WYE, 4 Wire, plus Ground
This section provides basic installation instructions for the PM3 SPD. Per UL 1449 Paragraph 1.4, SPDs "are
intended for installation on the load side of the main overcurrent protection". Locate the SPD as close as possible to
the circuit to be protected to minimize the wire length. This will optimize SPD performance.
Note that these instructions are not intended to supercede local or national codes. The installation should be per-
formed by a licensed electrician. To install a PM3 SPD, refer to Figure 3 and proceed as follows:
1. Unpack and inspect the unit for signs of damage. If the unit is damaged, contact APC Customer Service (at 1-800-
800-4APC). See Page 14 for obtaining service under the Warranty.
2. Locate where the SPD will be installed. Ensure the wire lengths from the SPD to the service panel are kept to a
minimum.
3. Carefully remove the front cover by loosening the four (4) captive screws that secure the front cover to the chassis.
Insure the ribbon cables attached to the diagnostic faceplate are not mechanically stressed or become unplugged.
DO NOT ALLOW THE DIAGNOSTIC FACEPLATE TO HANG BY THE RIBBON CABLES!
4. Two holes are provided for the installation of wiring. The unit is shipped with a three (3) piece plug for use in
plugging the unused hole. If the desired hole is plugged, remove the plug by removing the wing nut along with the
inner and outer plug pieces.
5. In order to keep wiring length and bend radii at a minimum, APC recommends that wiring be installed through the
left side of the SPD. APC also recommends that the hole be sealed with putty after wiring installation.
6. Drill four (4) pilot holes (mounting holes in the SPD are 5/16" in diameter) to provide for mounting of the SPD.
Page 5
:$51,1*
9(5,)<7+$ 7$//32:(5
&,5&8,76$5('((1(5*,=('
%()25(0$.,1*&211(&7,216
All electrical connections should be performed by a qualified (licensed) electrician. All wiring
must comply with the National Electric Code (NEC) and applicable local codes.
Page view 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 16 17

Comments to this Manuals

No comments