System Electrical Information
6Symmetra® PX 10-80 kW 208 V Site Preparation Guide - 990-1425A
This UPS system has no built-in disconnection devices for AC output and DC input. An AC output
over-current protection and AC output disconnect must be provided by the customer. For customer-
supplied external batteries, over-current protection and a disconnecting device for the battery circuits
must also be provided by the customer.
EPO switch wiring (required)
The UPS is to be connected to either a dry contact or a 24Vdc Emergency Power Off (EPO) switch.
The EPO circuit is considered Class 2 and SELV (Safety Extra Low Voltage). A SELV circuit is
isolated from primary circuitry through an isolating transformer and designed so that under normal
conditions, the voltage is limited to 42.4Vac peak or 60Vdc. SELV and Class 2 circuits must be
isolated from all primary circuitry. Do not connect any circuit to the EPO terminal block unless it can
be confirmed that the circuit is SELV or Class 2.
Use one of following cables to connect the UPS to the EPO switch:
For installations in US
CL2Class 2 cable for general purpose use.
CL2PPlenum cable for use in a vertical shaft or from floor to floor.
CL2R Racer cable for use in dwellings and raceways.
CL2XLimited use cable for dwellings and raceways.
For installations in Canada
CL2RCertified, type ELC (Extra-Low-Voltage Control Cable).
CL2XCertified, type ELC (Extra-Low-Voltage Control Cable).
Option: 10-80 kW Battery Enclosure
Option: 10-80 kW Battery Enclosure
Battery voltage (nominal) +/- 192 V
Battery current (at full load) 223 A at +
192 V
Max. current (at end of discharge) 266 A at +
160 V
If battery enclosure is customer-supplied, refer to product-specific data.