Discharge or Charger Inactive. Minor Alarm. The BMS detects 5 amps of
continuous discharge current on either battery string for more than 5
seconds.
Charger Voltage Low. Minor Alarm. After a discharge or application of
power, the Charger Voltage Low alarm condition is ignored for 60 minutes.
After the 60-minute delay, the Charger Voltage Low alarm occurs if the
string voltage value (the sum of all battery voltages in the string) is below
the string voltage limits.
Possible Causes Corrective Action
Loss of AC to power supply • Restore AC input before batteries are exhausted.
Power supply overloaded • Check for short circuits on load
• Remove excess load on system
Current sensor entered
calibration mode during a
battery charge
• Re-calibrate current sensor(s) by performing calibration
with no current flowing.
Current sensor installation
reversed
• If a discharge is indicated while the batteries are
charging, reverify orientation of sensor and reverse if
not installed correctly.
Possible Causes Corrective Action
Power supply charger
setting too low or failure of
charger temperature
compensating circuit
• Check charging system.
• Reset charger voltage or repair if required.
Incorrect temperature
compensation selected
• Verify that the configured temperature compensation
method (ambient or battery) matches the power
supply’s compensation method.