InRow RD Technical Data Manual28
Electrical Data
SKU MCA MOP FLA
Compressor
Power
LRA RLA
ACRD100
208-240V, 60Hz
25 40 N/A 87.5 16.0 4.6
ACRD101
220-240V, 50Hz
N/A N/A 21 97.0 16.3 4.4
ACRD200
208-240V, 60Hz
25 40 N/A 87.5 16.0 4.6
ACRD201
220-240V, 50Hz
N/A N/A 21 97.0 16.3 4.4
ACRD500
200-240V, 50/60Hz
54.0 90 - 160* 50 15
ACRD501
460-480V, 60Hz
27.0 40 - 139* 23.2 16
ACRD502
380-415V, 50Hz
- - 26.0 139* 23.2 16
Note: Above data is based on maximum operating condition
Note: Installation must comply with national and/or local electrical codes.
Note: Use LRA for estimation of inrush current.
* The compressor is powered by the VFD.
MCA-Minimum Circuit Ampacity
MOP-Maximum Overcurrent Protection
LRA-Compressor Locked Rotor Amps
RLA-Compressor Rated Load Amps
FLA-Full Load Amps