APC IN ROW RD ACRD101 Service Manual Page 31

  • Download
  • Add to my manuals
  • Print
  • Page
    / 56
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 30
25InRow RD Technical Data Manual
Air Cooled
Data SKU Value
AIR SYSTEM - FAN (Standard Filter Installed)
Size - mm (in)
ACRD100 200 (7.9)
ACRD101 200 (7.9)
ACRD500 series 400 (15.8)
Air Volume - l/s (SCFM)
ACRD100 1080 (2290)
ACRD101 1080 (2290)
ACRD500 series
2124 (4500)
Fan Motor - W (HP) each
ACRD100 115 (0.15)
ACRD101 115 (0.15)
ACRD500 series 1100 (1.5)
Number of Fans
ACRD100 series 6
ACRD500 series 2
COOLING COIL - COPPER TUBE/ALUMINUM FIN
Face Area - m
2
(ft
2
)
ACRD100
0.37 (3.97)
ACRD101
0.37 (3.97)
ACRD500 series
0.56 (6.0)
Rows Deep
ACRD100
2
ACRD101
2
ACRD500 series 4
FILTERS - WASHABLE (STANDARD)
Quantity
ACRD100 series
2
Size - mm (in) 238 X 933 (9.375 X 36.75)
Depth - mm (in) 13 (1/2)
Efficiency (%) <20% MERV 1
FILTERS - PLEATED (STANDARD)
Quantity
ACRD500 series
4
Size - mm (in) 418 x 470 (16.45 x 18.5)
Depth - mm (in) 101.6 (4)
Efficiency (%) 30
FILTERS - PLEATED (OPTIONAL)
Quantity
ACRD100 series
2
Size - mm (in) 238 X 933 (9.375 X 36.75)
Depth - mm (in) 51 (2)
Efficiency (%) 30% MERV 8
FILTERS - PLEATED (OPTIONAL)
Quantity
ACRD500 series
4
Size - mm (in) 418 x 470 (16.45 x 18.5)
Depth - mm (in) 101.6 (4)
Efficiency (%) 85
PHYSICAL DATA
Weight - kg (lbs)
ACRD100 series 183 (404)
ACRD500 series 367 (808)
Height - mm (in)
ACRD100 series 1991 (78.39)
ACRD500 series 1991 (78.39)
Width - mm (in)
ACRD100 series 300 (11.8)
ACRD500 series 600 (23.62)
Depth - mm (in)
ACRD100 series 1070 (42.13)
ACRD500 series 1070 (42.13)
CONNECTION SIZES
Refrigerant
Discharge
ACRD100 series 1/2 in ODF brazed
ACRD500 series 7/8 in ODF brazed
Maximum pressure drop - bar (PSI)
ACRD100
0.7 (10)
ACRD101
0.7 (10)
ACRD500 series 0.7 (10)
Liquid
ACRD100 series 1/2 in ODF brazed
ACRD500 series 7/8 in ODF brazed
Condensate Drain
Drain Line - in
ACRD100 series 3/16-in ID, 5/16-in OD
ACRD500 series 1/2
REFRIGERANT
Type
ACRD100 series R410A (amount determined at installation)
ACRD500 series R407C (amount determined at installation)
Page view 30
1 2 ... 26 27 28 29 30 31 32 33 34 35 36 ... 55 56

Comments to this Manuals

No comments