APC Automatic Disconnect Switch User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
1-3
Safety Precautions
Ensure that you read and understand all of the safety information contained in “About This Manual”, in the
front of this manual. If you have any questions concerning any of the safety information, or if you are
concerned that your home or office may not be properly wired for this equipment, contact a qualified and
licensed electrician, and APC Technical Support.
Unit Power
The UTS6 and UTS6BI are rated for 20 A (continuous), and the UTS10BI is rated for 30 A (continuous)
while on
BACKUP1 (generator). However, they are designed to support component inrush currents that
are much higher than their continuous power ratings. The UTS6BI and UTS10BI models are designed to
operate with a 120V/240V load. The UTS6 is only intended for 120V circuits and loads. Also note that
BACKUP2 (UPS) is 15 A or less.
Supporting 240V Circuits
An example of a 240V application would be a well pump. Most well pumps with 1/4 horse power (HP)
motors or greater require 240V, 2-pole (also called “split phase”) power. Models UTS6BI and UTS10BI
are designed to operate with both 120V and 240V loads. However, you must follow these 240V rules:
Only one 240V circuit can be backed up through the UTS. However, multiple 240V loads can be wired
to that 240 V circuit if required. Consult with a licensed electrician and APC Technical Support for
additional information.
A 240V circuit will use two UTS circuits. These are Circuits 9 and 10 for the UTS10BI, and Circuits 5
and 6 for the UTS6BI.
The 240V circuits are only powered from the
Backup1 (generator) source.
Supporting 120V Circuits
Most of the circuits and loads in your home or office will be 120V, single pole. Other than the 240V circuit,
all other UPS circuits are 120V circuits. The number of 120V circuits supported by each of the UTS
models are summarized below.
The following rules must be observed for 120V circuits and loads:
The 120V circuits should be balanced between Phase 1 and Phase 2 of the incoming generator power for
safe operation, and to ensure optimal backup generator operation.
If you use a second backup source (for example, a UPS) please note that Circuit1, which also powers the
convenience outlet for the UPS, only works with generator (
GEN) as the backup power source. All other
120V circuits can be backed up by the UPS source.
Note There is also a “hard wiring” option (Part No. UTSHW) to support up to 50 A
generators.
Model
Number of
120V Circuits
Circuits Used for
240V
UTS6BI Four (1 - 4) 5 and 6
UTS6 Six (1 - 6) N/A
UTS10BI Eight (1 - 8) 9 and 10
!
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 35 36

Comments to this Manuals

No comments