Site Preparation & Installation Guide Universal Transfer Switch UTS6 UTS6H UTS6BI UTS10BI4
UTS Specifications UTS6/UTS6H UTS6BI UTS10BI
Output
Nominal voltage
120 Vac circuits
120 Vac six total 120 Vac four total 120 Vac eight total
Nominal voltage
240 Vac circuits
N/A 240 Vac
one across Phase A & B
240 Vac
one across Phase A & B
Current per circuit 20 A maximum 20 A maximum 20 A maximum
Current for circuits combined 60 A maximum 60 A maximum 100 A maximum
Convenience outlet type NEMA 5-15 female
120 Vac 15 A
NEMA 5-15 female
120 Vac 15 A
NEMA 5-15 female
120 Vac 15 A
Protection
APC recommends that a
licensed electrician replace
blown fuses.
All models use UL-Listed Class CC Branch rated fuses 15 A or 20 A
Approved 15 A fuses Use ONLY Ferraz-Shawmut ATMR15
Approved 20 A fuses Use ONLY Ferraz-Shawmut ATMR20
Environmental
Operating temperature -25º C to 40º C
-13º F to 104º F
-25º C to 40º C
-13º F to 104º F
-25º C to 40º C
-13º F to 104º F
Operating humidity 5% to 95% 5% to 95% 5% to 95%
Storage temperature -40º C to 85º C
-40º F to 185º F
-40º C to 85º C
-40º F to 185º F
-40º C to 85º C
-40º F to 185º F
Operating Elevation,
maximum
3000 m (10,000 ft) 3000 m (10,000 ft) 3000 m (10,000 ft)
Storage elevation, maximum 15000 m (50,000 ft) 15000 m (50,000 ft) 15000 m (50,000 ft)
Physical - install the UTS within one foot of the building circuit breaker panel
Unit dimensions 39.4 x 49.8 x 8.3 cm
15.5 x 19.6 x 3.3 in
39.4 x 49.8 x 8.3 cm
15.5 x 19.6 x 3.3 in
39.4 x 59.4 x 8.3 cm
15.5 x 23.4 x 3.3 in
Unit weight 21.5 lbs 21.5 lbs 27.5 lbs
Packaged dimensions 18.7 x 22.9 x 8.4 in 18.7 x 22.9 x 8.4 in 18.7 x 26.8 x 8.4 in
Packaged weight 25 lbs 25 lbs 31 lbs
Generator Interface - Automatic, Remote Start/Stop
Generator Start/Stop Individual separate relay contact closure; programmable, normally open (NO) and
normally closed (NC)
Start Delay 30 sec to 60 min 30 sec to 60 min 30 sec to 60 min
Stop Delay 30 sec to 60 min 30 sec to 60 min 30 sec to 60 min
Generator Exercise (Test) Every two weeks Every two weeks Every two weeks
Options & Accessories
APC UTS Automatic Remote Start/Stop Kit
Spare fuses