TransfertheUPSintoMaintenanceBypassOperation
Note:Ifshutdownviathedisplayisdisabled,thenyoucannotperformthisprocedureand
themessage:Commandnotallowed,UPSconguredtonevershutdownappears.If
youwanttoenableshutdownviathedisplay,thisisdonebyanFieldServiceEngineer
viatheUPSTuner.
1.SelectUPSandpressENTER.
UPSAlarms
PowerDistLog
SwitchGearAdmin
EnvironmentHelp
2.SelectUPSPowerControlandpressENTER.
UPSPowerControl
UPSStatus
UPSTests&Diags
UPSConfiguration
3.SelectUPSintoBypassandpressENTER.
TurnUPSOff
RebootUPS
UPSintoBypass
UPStoSleep
4.SelectY es,IntoBypassandpressENTER.
Confirm:
UPSintoBypass?
NO,ABORT
YES,IntoBypass
5.Waitforthetransfertocomplete.
PuttingUPSinto
Bypass,please
wait....
6.Conrmthatthetransfertobypassiscomplete.
Note:TheH3LEDnexttotheQ3
switchwillturnon,indicatingthatit
isoktooperatetheQ3switch.
UPSisnowin
Bypass.
Pressanykey....
7.SettheQ3switchtotheONposition.
Note:TheH2LEDbesidetheQ2
switchwillturnon,indicatingthatit
isoktooperatetheQ2switch.
8.SettheQ2switchtotheOFFposition.