APC Rack PDU Extender, Basic, 2U, 30A, 100/120/200/208V Specifications Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
Rack Power Distribution Unit 11
Specifications
Electrical
Nominal input voltage 120 or 208 V
Input frequency 50 or 60 Hz
Input connectors NEMA L14-30 plug
Output connectors AP7580: Four NEMA L5-20 outlets
AP7581: Four NEMA L6-20 outlets
AP7582: Twelve NEMA 5-20 outlets
AP7583: Four NEMA L5-30 outlets
AP7584: Four NEMA L6-30 outlets
Maximum total current draw 24 A
Physical
Size (H × W × D)
3.50 ×17.20×3.50 in
(8.89×43.69×8.89 cm)
Weight 14.0 lb (6.4 kg)
Shipping weight 16.0 lb (7.3 kg)
Environmental
Elevation (above MSL)
Operating
Storage
010,000 ft (03000 m)
050,000 ft (015 000 m)
Temperature
Operating
Storage
0 to 45° C (32 to 115° F)
–25 to 65° C (–13 to 149° F)
Humidity
Operating
Storage
095%
RH Non-condensing
095%
RH Non-condensing
Compliance
Safety verification UL, cUL