APC Redundant Switch: Installation and Operation Manual 15
Operation
Controls,
LED
s,
and ports on the
front panel
Storage
Note
APC
recommends the factory default settings
among the settings shown below.
Function LED Display Description
Source
A
Sensitivity
Bright= Normal
Dim (the factory
default) = Reduced
Off = low
Sets transfer
sensitivity to line
conditions
Source
B
Sensitivity
Source
Preference
Bright = Source
A
(the factory default)
Dim = Source
B
Off = none
Selects the preferred
AC
source
Source
A
Xfer
Voltage
Bright = Narrow
Dim = Medium (the
factory default
Off = Wide
Sets the transfer
voltage window (the
range of acceptable
voltage)
Source
B
Xfer
Voltage
Redundant Switch
Page view 18