990-4768 Smart-UPS On-Line, 208 V/240 V, 1.5kVA to 20kVA Technical Specifications 25
Facility Planning
Specifications for Installations
AC Input
Input Voltage and Connections Specifications
UPS VA
1500
2200
3000
5000
6000
8000
10,000
15,000
20,000
Input
Frequency
45 - 65 Hz (auto sensing)
40 - 70 Hz (auto-
sensing)
Nominal Input
Voltage
120 V
120 V or
208 V
208 V
Current, Full
Load (Nominal)
10.2 A
13.3 A
20.7 A @
120 V;
11.6 A @
208 V
18.2 A
20 A
40 A
48 A
80 A
100 A
Bypass
Automatic
Automatic and Manual (Built-In)
Input
Connections
5-15P
5-20P
L5-30 or
L6-30P
L6-30P
Hard Wire 3-wire (2PH + G)*
Wire Size
(typical)
Not applicable
10 mm
2
#8 AWG
16 mm
2
#6 AWG
25 mm
2
†‡
#2 AWG
35 mm
2
†‡
#1 AWG
External Input
Circuit Breaker
(typical)
Not applicable
30/32 A
50 A /
2-pole
60 A or
63A /
2-pole
100 A /
2-pole
125 A /
2-pole
* Wire connection “G” represents protective earth ground.
Wire gauges may vary. Adhere to national and local electrical codes when wiring this unit.
Terminal screw tightening torque: 40 lb-in (45 N-m)