Page 4
2. OSHPD Pre-approval: In addition to the preceding regulatory approvals, the APC
Smart-UPS RT 3 kVA RM 230 V model (SURTD3000RMXLI) and the APC Smart-
UPS RT 5 kVA RM 230 V model (SURTD5000RMXLI) have OSHPD pre-approval
(pre-approval by California Office of Statewide Health Planning and Development)
when used in any of three APC NetShelter
TM
enclosures:
a. APC NetShelter SX 42 U Enclosure (Commercial), AR3100SP1
b. APC NetShelter VX Seismic 42 U Enclosure (Seismic), AR3100SP1
c. APC NetShelter 2-Post Rack 45 U (Commercial), AR201
1.4 SYSTEM DESCRIPTION
A. Mechanical Design
1. The UPS is contained in a rugged steel cabinet with plastic front bezels:
2. The UPS dimensions are:
APC Smart-UPS RT 1000 VA RM 230 V
APC Smart-UPS RT 1000 VA 230 V
APC Smart-UPS RT 1000 VA 230 V –
Marine
APC Smart-UPS RT 2000 VA RM 230 V
APC Smart-UPS RT 2000 VA 230 V
APC Smart-UPS RT 2200 VA 230 V –
Marine
APC Smart-UPS RT 3000 VA 230 V with
Pre-installed Input/Output Hardwire Kit
APC Smart-UPS RT 3000 VA RM 230 V
APC Smart-UPS RT 3000 VA 230 V
APC Smart-UPS RT 3000 VA 230 V –
Marine
APC Smart-UPS RT 5000 VA RM 230 V
APC Smart-UPS RT 5000 VA 230 V
APC Smart-UPS RT 5000 VA 230 V with
Pre-installed Input/Output Hardwire Kit
APC Smart-UPS RT 6000 VA RM 230 V
APC Smart-UPS RT 6000 VA 230 V
APC Smart-UPS RT 6000 VA, 230 V with
Pre-installed Input/Output Hardwire Kit
APC Smart-UPS RT 6000 VA 230 V –
Marine
APC Smart-UPS RT 8000 VA RM 230 V
APC Smart-UPS RT 8000 VA 230 V
APC Smart-UPS RT 10,000 VA RM 230 V
APC Smart-UPS RT 10,000 VA 230 V
APC Smart-UPS RT 15 kVA RM 230 V
APC Smart-UPS RT 20 kVA RM 230 V
3. The UPS cabinet is capable of conversion between Tower and Rack-Mount
configurations.
B. System Characteristics:
1. System Capacity: The system is rated to be capable of supporting:
a. 1 kVA or 700 W, whichever limit is reached first (for the 1 kVA models).
b. 2 kVA or 1400 W, whichever limit is reached first (for the 2 kVA models).