APPLICATION NOTE
Fig. 3: Top: Output voltage on the diesel generator.
Bottom: Output voltage on 480kW. Here 480kW is loaded with 100% resistive load.
A number of measuring on the 480kW supplied from diesel generator has been carried out. Fig. 1 and 3 show that the ramp-in
time on the generator has an influence on how much the frequency on the generator decreases at ramp-in and on how much
the frequency changes when the ramp-in ends. Therefore some additional tests have been carried out on the 480kW, showing
that if a long ramp-in time is chosen, then the slew rate can be de-creased. This is important if a short ramp-in time is wanted,
because then a higher slew rate time has to be accepted. By installation of systems with diesel generator, both slew rates as
well as ramp-in time have therefore to be adjusted to the used generator. The total conclusion is that 480kW has handled the
diesel operation to satisfaction.
Requirements of the diesel generator
When dimensioning the diesel generator for an APC Silcon UPS is aware of the following recommended requirements:
kVA rating
As APC Silcon has PF 1 on the input, there is no requirement of kVA rating of the generator.
kW rating
When APC Silcon is going to operate on the diesel generator, the batteries of the APC Silcon UPS have already been
discharged. Therefore the generator must take over full charging power, loss in inverter, as well as load.
On figure 4 the input current of the APC Silcon can be calculated using table and curve.