TTACH THE BEZEL TO THE UPS
5000/6000
VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS
Wiring must be performed by a qualified electrician.
Adhere to all national and local electrical codes.
Install a high magnetic 30/32 A utility circuit breaker
Use #10 AWG gauge (5sq. mm) wire.
1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.
4. Run #10 AWG gauge (5sq. mm) wire through the access panel, and connect the wires to the
terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief
(not included).
5. Replace the access panel.