Installation—Accessories
10 Temperature/Humidity Module
Connecting TH Modules
To connect the Main Module to the TH Module:
1. Connect the first TH Module to either port
marked A-Link on the rear of the Main
Module, using a standard CAT5 (or
equivalent) Ethernet patch cable (APC part
number 3827BK-10 or equivalent). Do not use
a crossover cable for connection.
2. Connect the cable from the Main Module to
the top A-Link connector labeled
(indicating “input”) on the TH Module.
Connect the bottom A-Link connector labeled
(indicating “output”), to the next TH
Module.
3. Plug an APC terminator (0W04161) into the
unused A-Link port at each end of the string.
The Main Module does not have to be at the
beginning of the chain of cascaded modules. You
can cascade TH Modules from both A-Link ports
of the Main Module. Always connect the
Environmental Manager to the input connector on
the TH Module, as described in step 2.
Note
A-Link is an APC proprietary CAN
(Controller Area Network) bus.
Devices compatible with A-Link are
not Ethernet devices and cannot
coexist on an Ethernet bus with other
networking devices, such as hubs and
switches.
Note
The maximum combined length of all
A-Link cables is 3280 ft (1000 m).
Note
It is not possible to cascade Main
Modules. Install only one Main
Module per system.