CHAPTER 1: SAFETY AND GENERAL INFORMATION
2
De-energizing Safety
To de-energize this equipment toggle the rear input circuit breaker to the OFF position, and then
disconnect the equipment from the AC power outlet.
Electrical Safety
The protective earth conductor carries the leakage current from the load devices (computer
equipment). Therefore, the size of the conductor must be at least as large as the wire required
by IEC 950. An insulated grounding conductor that is identical in size, insulation material, and
thickness to the grounded and ungrounded branch-circuit supply conductors, except that it is
green with or without a yellow stripe is to be installed as part of the branch.
The grounding conductor described above is to be grounded to earth at the service
equipment, or if supplied by a separately derived system, at the supply transformer or motor-
generator set.
The attachment-plug receptacles near the unit or subsystem are all to be of a grounding type,
and the grounding conductors serving these receptacles are to be connected to earth ground
at the service equipment.
To reduce the risk of fire, connect only to a circuit provided with 30-amp maximum branch
circuit overcurrent protection in accordance with the National Electrical Code, ANSI/NFPA.
Regulatory Agency Approvals
Regulatory Agency Symbols
LISTED 42C2
E95463
LR63938
(AP9621,
SYTF2, SYTF3
ONLY)