APC BC300 Series Installation Guide Page 20

  • Download
  • Add to my manuals
  • Print
  • Page
    / 38
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 19
20 Installation Guide APC BC300 Series 15kW 208/450/480V UPS
990-1165
Installation
Figure 12
Utility Source (Provided by Others)
450V 3 Wire + Ground
MIB
Service
Bypass
Panel
Q001
UIS
F4, 5, 6
UIF
UPS
F1, 2, 3
UOF
Q002
UOS
Q003
BS
UPS System Output
450V 3 Wire & Ground
Notes:
1. Must be 3 wire + Ground
2. Must be 3 wire + Ground cabling
provided by others.
3. Input overcurrent protection is based on
80% rating - any deviation, please contact
APC.
4. F1, F2, F3 = 25A
5. F4, F5, F6 = 30A
6. All AC power cabling is 3 wire + Ground
at 208VAC 3-phase.
7. UPS output cables and input cables must
be in separate conduits.
8. Power wiring and control wiring must be
in separate conduits.
9. See installation manual for battery
information.
10. Installation must comply with all
applicable national and local codes.
26A
26A
19A
40A.T.
19A
19A
15kW