APC SYMMETRA MW II User Manual Page 10

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 9
10
More information about the Symmetra
®
MW is available at www.apc.com
Symmetra
®
MW Battery Breaker Box
Part No. SYMW400KHBB630A** SYMW600KHBB1000A**
General Specifications
Nominal Current (400 V) 520 A 781 A
Maximum Current (400 V) 613 A 920 A
Nominal Voltage 2* 384 V 2* 384 V
Physical
Dimensions (HxWxD) mm 2016x768x628 2016x1160x628
Weights (kg) 143 200
Minimum clearance around Top clearance 500 mm (200 mm in installations with IP21 Drip Cover). Front clearance 1000 mm.
Battery Breaker Box
Color Grey (NCS 2703-G85Y), Black (NCS S 9000-N)
Seismic anchoring Yes
Seismic zone No
Protection
Surge IEC-1000-4-5, EN50091-2
Thermal Yes
Short circuit Yes
Regulatory
Safety IEC60950 3rd edition, EN50091-1-1-1
EMC/EMI/RFI EN50091-2
Approvals CE, ISO 9001, ISO 14001
Symmetra
®
MW External Bypass Static Switch
Part No. (Cable Entry, top/bottom) SYSWT1000KH (top)/ SYSWT2000KH (top)/ SYSWT3000KH (top)/ SYSWT4000KH (top)/
SYSWB1000KH(bottom) SYSWB2000KH (bottom) SYSWB3000KH (bottom) SYSWB3000KH (bottom)
Power Range (MW/MVA) 1 2 3 4
General Specifications
Nominal Voltage 3x400/230 V (L1,L2,L3,N,PE)
Nominal Current (400 V) 1443 A 2887 A 4330 A 5773 A
Tolerance (programmable) ±4%, ±6%, +/-8%, ±10%, standard ±10%
Frequency (programmable) 50 Hz ±0.5-8% (display setup)
Max short-circuit withstand level (l
cw
) 200 kA 200 kA 100 kA 100 kA
Overload capacity 125% continuous
Communication and Management
Control Panel Advanced 10” Colour LCD Touch-Screen User Interface
Audible Alarm Audible and visible alarms prioritized by severity
Emergency Power Off (EPO) Yes
Emergency Module Off (EMO) Yes
Indicators and Controls Self diagnosing with surveillance of fuses, fans, batteries, temperatures etc.
Physical
Dimensions (HxWxD) mm 2032x1016x1067 2032x1016x1067 2032x2114x1067 2032x2114x1067
Minimum clearance around Top clearance 500 mm (200 mm in installations with IP21 Drip Cover). Front clearance 1000 mm.
External Bypass Static Switch
Color Grey (NCS 2703-G85Y), Black (NCS S 9000-N)
Seismic Anchoring Yes
Seismic Zone No
Weights (kg) 470 620 1240 1240
Protection
Surge IEC-1000-4-5, EN50091-2
Thermal Yes
Short circuit Yes
Regulatory
Safety IEC60950 3rd Edition, EN50091-1-1
EMC/EMI/RFI EN50091-2
Approvals CE, ISO 9001, ISO 14001
Audible Noise
Audible noise, nom max. at 71 74 77 77
1 m from unit (dB(A))
* Includes External Bypass Static Switch
** Not standard SKU, should be ordered through Customer Engineering Group
Page view 9