External Baying Kit AR8376, AR8376BLK, AR8377BLK
10 External Baying Kit AR8376, AR8376BLK, AR8377BLK
Follow this procedure when joining two NetShelter VX enclosures.
Enclosures configured on 24-inch D
centers:
1. Align the hole D in the VX baying
plate
with the hole in the right
vertical frame of the enclosure to
the left. Insert and tighten a low-
profile screw.
2. Align the hole F in the VX baying
plate
with the hole in the left
vertical frame of the enclosure to
the right. Insert and tighten a low-
profile screw.
Enclosures configured on 600-mm E centers:
1. Align the hole E of the VX baying plate
with the hole in the right vertical frame of the
enclosure to the left. Insert and tighten a low-profile screw.
2. Align the hole F of the VX baying plate
with the hole in the left vertical frame of the
enclosure to the right. Insert and tighten a low-profile screw.
,
-
.