10
Setup
continued
Switch types:
Table 4
The requirements and PIN assignments for the remote
switch vary according to the type of switch being used:
Keystone jack
PIN locations:
Figure 5
The PIN locations for the keystone jack appear in the figure
below.
Figure 5 :keys tone jack PIN locati ons
Continued on next page
Type Requirements
RPO/Cascade In
PIN Assignment
Contact
Closure
Safety Extra Low Voltage
(SELV) or Class 2 circuit
Switch or relay properly
isolated from the utility
Latching
2, 5
Voltage
Input
SELV or Class 2 circuit
Switched 24V AC/DC
Latching
3, 4
Table 4: Switch types