NetBotz Rack Monitor 450/550/570 Installation and Quick Configuration Manual10
Connect Sensors and Sensor Pods to A-Link Ports
With a NetBotz 550 or NetBotz 570, you can cascade up to a combined total of twelve NetBotz Rack
Sensor Pod 150s (NBPD0150) and NetBotz Room Sensor Pod 155s (NBPD0155) plus up to a combined
total of eight Temperature Sensors with Digital Display (AP9520T) and Temperature/Humidity Sensors
with Digital Display (AP9520TH).
With a NetBotz 450, you can cascade up to a combined total of two NetBotz Rack Sensor Pod 150s
(NBPD0150) and NetBotz Room Sensor Pod 155s (NBPD0155), plus up to a combined total of eight
Temperature Sensors with Digital Display (AP9520T) and Temperature/Humidity Sensors with Digital
Display (AP9520TH).
You cannot cascade appliances. Use one appliance per system. A-Link is an APC proprietary CAN
(Controller Area Network) bus. Devices compatible with A-Link are not Ethernet devices and cannot
coexist on an Ethernet bus with other networking devices, such as hubs and switches.
Before performing this procedure, follow the installation instructions provided with the devices you are
cascading. Also, if you cascade more than ten sensor pods, be sure you have a supplemental power
supply (Power Supply 100-230 VAC/24 VDC—AP9505i) to connect to your system as directed in this
procedure. The NetBotz 570 does not require an external power supply.
1. Connect sensors and sensor pods to the
appliance as shown.
Use CAT-5 (or equivalent) Ethernet
patch cables (

. Caution: Do not
use crossover cables.
Connect to in and out ports as shown.
The maximum combined length of all
A-Link cables must not
exceed 1000 m (3,280 ft).
2. Plug an A-Link terminator into the
unused A-Link port (
).
Caution: The first time a sensor pod receives power, it obtains a unique
identification address for communication over the A-Link bus. To avoid
communication problems, you must complete steps 1 and 2 before you connect a
supplemental power supply.
3. With a Rack Monitor 450 or 550, if you have cascaded ten or more devices, connect one
supplemental power supply (AP9505i) to the 24 VDC Input jack of the Rack Sensor Pod 150 or
the Room Sensor Pod 155 in or closest to the eleventh position.
(NBRK0450)
(NBPD0150)
Rack Sensor
Pod 150
NetBotz
NetBotz Rack
Monitor 450
(NBPD0150)
Rack Sensor
Pod 150
NetBotz
(AP9520TH)
Humidity
Sensor
Temperature/