7NetBotz Rack Sensor Pod 150 Installation Manual
Connect Sensors
Only connect sensors supported by the appliance to which the NetBotz 150 is connected. See the
installation and quick configuration manual included with your appliance.
Caution: Only connect approved devices to ports on the NetBotz 150 as directed in this
manual. Plugging in other devices may result in equipment damage.
Connect APC and third-party sensors to the six ports labeled Sensors on the NetBotz 150.
Third-party dry contact sensors require the NetBotz Dry Contact Cable (NBES0304). To connect
a sensor to the cable, follow the instructions provided with the sensor and the instructions
provided with the cable.
Standard third-party 0-5 V sensors require the NetBotz 0-5 V Sensor Cable (NBES0305). To
connect a sensor to the cable, follow the instructions provided with the sensor and the instructions
provided with the cable.
If a sensor cable is not long enough, use an RJ-45 coupling (provided with some sensors) and
standard CAT-5 cabling to extend the cable up to 15 m (50 ft) for a Temperature/Humidity Sensor
(AP9335TH) or a Temperature Sensor (AP9335T) and up to 30.5 m (100 ft) for all other
supported sensors.
Configure and Monitor Sensors
Once your system is installed and receiving power, configure sensors and begin monitoring your system
using the software interface for the appliance.
See your appliance installation and quick configuration manual for system installation details
and for instructions on accessing the software interface of the appliance.
Upgrade the NetBotz 150
Firmware upgrades for NetBotz 150s are included with firmware upgrades for NetBotz appliances.
When you upgrade firmware for the appliance to which the NetBotz 150 is connected, the NetBotz 150
firmware will be updated automatically, if required.
Note: The NetBotz 150 Identifier # LED shows 88 during a firmware upgrade. During the
upgrade, data from sensors connected to the NetBotz 150 will be invalid.
For more information on firmware upgrades, see your appliance user’s guide. For details on
how to access your appliance users guide, see “Additional documentation” on page 1.
Clean the NetBotz 150
To clean the device, gently wipe surfaces with a clean, dry cloth.