APC InfraStruXure InRow RC Service Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
4 APC InRow SC Technical Data Manual
Standard Features
Variable Speed
Direct Drive
Tubeaxial Fans
Each unit is
equipped with
six 200mm
mixed flow,
direct drive,
tubeaxial DC
fans. Three of the fans blow air
across the condenser coil to provide
heat rejection from the refrigerant
system. In order to provide uniform
airflow across the evaporator coil,
the remaining three fans draw air
through the evaporator section. The
evaporator fans can be easily
replaced while the unit is in opera-
tion. All fans are variable speed,
allowing them to assist in modulat-
ing unit cooling capacity and
maintaining refrigerant head
pressure.
Insulated Side Panels
The frame
is con-
structed of
16 gauge
formed
steel for
maximum strength. All exterior
panels and corner posts on the
frame are powder coated for dura-
bility and an attractive finish. Front
and rear exterior panels are con-
structed of 18 gauge perforated
steel with 69.5% open free area.
Insulation is 5 lb/ft
3
(80.1 kg/m)
density and complies with ASTM
E84 rating of 25/50.
Condensate Pump
Removes condensate from the sys-
tem to ensure continuous operation.
The factory installed and wired con-
densate pump is capable of
pumping 1.3g/hr (5.9l/hr) against
head pressures of up to 50ft (15.2m)
of total run, of that 16ft (4.9m) can
be vertical lift.
Condensate Pan
Condensate Pan is fabricated from
V-0 polymeric materials and is ther-
mal formed, provided with
antifungal additives, and is a non-
ferrous material for higher indoor
air quality.
Electronic Hot Gas Bypass
An electronically controlled hot gas
bypass valve directs hot discharge
gas from the compressor back to the
expansion valve and into the coil.
During lightly loaded conditions,
compressor cycling is reduced and
prevents the evaporator coil from
freezing. Hot gas bypass also assists
in the management of the refriger-
ant head pressure.
Single Cord Power Supply
The 60hz unit utilize a NEMA L6-
20 plug, the 50hz unit uses an IEC
309 16A plug. The power cord can
be connected to the power feed
either through the top or bottom of
the unit.
Network Management Card
Permits multi-level access to moni-
toring, control, and event
notification features over the user’s
network. Also allows the InRow SC
to be integrated into APC’s InfraS-
truXure Manager device.
High Head Pressure Protection
The condenser fans modulate to
maintain a nominal refrigerant dis-
charge of 425 PSIG (6.9kPa). If the
condenser inlet air is restricted or
too warm, the refrigerant discharge
pressure will rise forcing the con-
denser fans to increase speed to
100%. To prevent a total loss of
cooling, the unit will slow evapora-
tor fans and begin to activate the hot
gas bypass valve to reduce system
capacity. If the discharge pressure
continues to rise, the unit will shut
down in order to prevent unit
damage.
Rack Inlet Temperature Control
To control the unit based on rack
inlet temperature, a remote sensor is
provided. This sensor is factory
wired for a remote placement in the
field on adjacent IT racks.
Remote Shutdown/IO Contacts
The unit provides one field connec-
tion input for remote shutdown. I/O
contacts allow for remote annuncia-
tion of any alarm condition or
critical only alarms.
Dual Fan Power Supply
The unit includes 2 power supplies,
each capable of running all fans at
80% capacity in the event of a sin-
gle power supply failure. Individual
power supplies are hot swappable.
Washable Filters
The filtration of conditioned air is
extremely vital to maintaining the
clean, particle-free environment
required by electrical equipment.
Filters are <20% efficient
(ASHRAE 52.1) and MERV 1
(ASHRAE 52.2) rated that meets
HF-1 standards for electronics.
Ducting Kit w/Ceiling Adapter
60Hz units have a 24in x 24in
adapter, 50Hz units have a
600mm x 600mm adapter. Each
duct tube is 6 ft. (1.8m) long and
10in (254mm) in diameter. Three
ducts are provided, one for the con-
denser supply and two for the
condenser exhaust. Mounting hard-
ware is provided to attach ducts to
the ceiling adapter.
SX Rack Baying Kit
Baying kit enables the cooling sys-
tem to be bayed to the APC
Netshelter SX enclosures. Kit is
made of 16 gauge steel.