5
Bypass input
Notes
1
Input current based on rated load and batteries fully charged.
2
Input current based on full battery recharge, nominal voltage and rated load.
3
Current limitation through electronic current limiting is based on full battery
recharge and low input voltage.
4
Synchronization adjustable: ± 10Hz, ± 3Hz or ± 0.1Hz.
Recommended current protection
Note: AC input/output over-current protection and AC
input/output disconnect must be provided by the customer
Recommended cable sizes
Note: The recommended cable sizes are based on an
environment with an ambient temperature of 30°C.
Note: Use Molex lug type or equivalent, and crimp to
manufacturer’s specifications.
Warning: At 100% switch mode load, the neutral must
be rated for 200% phase current.
Minimum breaker settings
Recommended lug size and torque value
Note: Power terminal lug diameter: 6 mm. Torque value: 7
Nm.
10 kVA
UPS ratings 380 V 400 V 415 V
Input frequency (Hz)
4
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
Nominal input current (A)
1
15.2 14.4 13.9
15 kVA 20 kVA
UPS
ratings
380 V 400 V 415 V 380 V 400 V 415 V
Input
frequency
(Hz)
4
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
Nominal
input
current
(A)
1
22.8 21.7 20.9 30.4 28.9 27.8
30 kVA 40 kVA
UPS
ratings
380 V 400 V 415 V 380 V 400 V 415 V
Input
frequency
(Hz)
4
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
50±10 or
60±10
Nominal
input
current
(A)
1
45.6 43.3 41.7 60.8 57.7 55.6
Q1
1
Q3 Q2
Utility input Bypass input Output
10 kVA
16 16 16
15 kVA
25 25 25
20 kVA
35 35 35
30 kVA
50 50 50
40 kVA
63 63 63
1
Required upstream current protection, mains input: gL type fuse.
.
Mains input
[mm
2
]
AC output
[mm
2
]
Battery input
[mm
2
] 75ºC
Wire
Bypass input
[mm
2
]
10 kVA
2.5 2.5 50 2.5
15 kVA
66506
20 kVA
10 10 50 10
30 kVA
16 16 50 16
40 kVA
25 25 50 25
800%
overload
bypass
operation
150%
overload
normal/
battery
operation
125%
overload
normal/
battery
operation Continuously
10 kVA
Mains input
1
–– 16.4 A
Bypass input 121.5 A 16.7 A
Output 121.5 A 22.8 A 19 A 16.7 A
Duration 500 ms 60 s 10 min.
15 kVA
Mains input
1
–– 24.6 A
Bypass input 182 A 25.1 A
Output 182 A 34.2 A 25.4 A 25.1 A
Duration 500 ms 60 s 10 min.
20 kVA
Mains input
1
–– 32.5 A
Bypass input 244 A 33.4 A
Output 244 A 45.6 A 38 A 33.4 A
Duration 500 ms 60 s 10 min.
30 kVA
Mains input
1
–– 49.1 A
Bypass input 364 A 50.1 A
Output 364 A 68.4 A 57 A 50.1 A
Duration 500 ms 60 s 10 min.
40 kVA
Mains input
1
–– 65.6 A
Bypass input 487 A 66.9 A
Output 487 A 91.2 A 76 A 66.9 A
Duration 500 ms 60 s 10 min.
1
At single feed use the higher value of mains and bypass.