NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE
FUNCTION
F
ACTORY
D
EFAULT
U
SER SELECTABLE
CHOICES
DESCRIPTION
Synchronized
Turn-on Delay
0 seconds 0, 60, 180, 300
seconds
Specify the time the UPS will wait
after the return of utility power before
turn-on (to avoid branch circuit over-
load).
High Transfer
Point
110/120 V model:
127 Vac
230 V model:
253 Vac
110/120 V model:
127, 130, 133, 136
Vac
230 V model:
253, 257, 261, 265
Vac
Set the high transfer point higher to
avoid unnecessary battery usage when
the utility voltage is usually high and
the connected equipment is specified
to operate with input voltages this
high.
Low Transfer Point 110/120 V model:
106 Vac
230 V model:
208 Vac
110/120 V model:
97, 100, 103, 106
Vac
230 V model:
196, 200, 204, 208
Vac
Set the low transfer point lower when
the utility voltage is usually low and
the connected equipment is specified
to operate with input voltages this low.