APC Smart-UPS 750 Specifications Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 12
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
7
For more information about all APC products, go to www.apc.com
1
Transfer points are user-adjustable using included software.
2
Servers and other IT equipment are moving to Power Factor Corrected (PFC) power supplies of 1.0, where the power drawn in Volt-Amps (VA) is equal to Watts(W). For accurate sizing, use the watt
rating of the equipment to determine the correct UPS and runtime. If the watt rating is unavailable use the Amp (A) rating and multiply by the voltage to obtain VA. For the most recent sizing information, please
consult the Size-UPS section of APC’s website at www.apc.com/sizing.
Smart-UPS
®
Rack-mount Series
Available in a broad range of sizes, Smart-UPS rack-mounts are easy to
install and compatible with all popular rack systems. They offer an ideal
solution for rack-optimized servers, server appliances, blade servers and
other rack mounted network switches, hubs and gateways.
New!
New!
New!
New!
New!
New!
New!
SPECIFICATION SUA750RMI1U SUA1000RMI1U SUA750MI2U SUA1000RMI2U SUA1500RMI2U SUA2200RMI2U SUA3000RMI2U SU5000RMI5U
PowerChute Support for Windows Server 2003/2000/NT 4.0, Novell Netware, Red Hat Linux, SuSE Linux, Turbolinux and Sun Solaris.
Business Edition 5 Node Version
Number of SmartSlot Bays 1 2
Input Line IEC320 C14 IEC320 C20 Hardwire
Output Receptacles (IEC320 C13) (8) IEC320 C13
4 C13, 2 Jumpers 8 C13, 1C19 & 3 jumpers (2) IEC320 C19
Maximum Dimensions (H x W x D) 438x432x660mm 88.9x483x457mm 88.9x483x660mm 222x483x635mm
Net Weight 21.8 kg 21.8 kg 28.2 kg 28.6 kg 43.6 kg 93 kg
Shipping Weight 25.5 kg 25.1 kg 31.6 kg 31.9 kg 56.8 kg 102 kg
Replacement Battery Cartridge RBC 34 RBC 22 RBC 23 RBC 24 RBC 43 (2) RBC 12
Service Level SB12 SB14
OPERATION SUA750RMI1U SUA1000RMI1U SUA750MI2U SUA1000RMI2U SUA1500RMI2U SUA2200RMI2U SUA3000RMI2U SU5000RMI5U
Nominal Input Voltage 230 Vac, single phase, 50 or 60 Hz (auto-selectable)
Transfer Time (typical) 2 milliseconds, includes detection time
AVR Boost/Trim 30% / 12% 12% / 12%
Default Input Voltage Range 160-286 Vac 174-286 Vac
Max input voltage adjustable range
for mains without battery discharge
1
151-302 Vac 168-302 Vac
Output Voltage Range 208-253 Vac 196-253 Vac
Capacity (Volt-Amps, Watts) 750, 480 1000, 640 750, 480 1000, 670 1500, 980 2200, 1980 3000, 700 5000, 3750
Surge energy rating, peak current 480 Joules, 6.5kA
Normal, common mode clamping 0 ns, <5ns typical
response time
Normal mode surge voltage let <0.3% of peak typical
through (IEEE 587 Cat. A 6kV test)
Batteries Maintenance-free sealed Lead-Acid with a 3-6 year typical lifetime: leakproof
Recharge time to 90% capacity 2 hours 3 hours
Ambient Operation 3,000 meters max. elevation, 0-95% humidity non-condensing 0-40 deg. C
Storage Conditions 15,000 meters max. -15-45 deg. C
Audible noise at 1 meter <45 dBA <36 dBA <46 dBA <47 dBA <53 dBA
BTUs/hr. 130 68 89 171 300 400 430
TYPICAL RUNTIME
2
LOAD SUA750RMI1U SUA1000RMI1U SUA750MI2U SUA1000RMI2U SUA1500RMI2U SUA2200RMI2U SUA3000RMI2U SU5000RMI5U
Watts (VA)
195 300 31min 31min 23min 1hr 4min 1hr 21min 1hr 38min 1hr 46min 4hr 39min
455 700 10min 10min 7min 24min 37min 47min 52min 2hr32min
650 1000 - 6min - 11min 19min 30min 33min 1hr 38min
910 1400 - - - - 9min 18min 20min 59min
1040 1600 - - - - - 12min 13min 40min
1430 2200 - - - - - 10min 11min 31min
1950 3000 - - - - - - 6min 17min
3500 5000 - - - - - - 6min
Page view 6
1 2 3 4 5 6 7 8 9 10 11 12

Comments to this Manuals