Smart-UPS C 1000/1500 VA 120 Vac Tower6
LED status indicators
LCD status indicators
System Faults
The Smart-UPS will display a fault message in the event of an internal system fault.
Status LED Audible Indicator On
Audible Indicator
Terminates
Power On
The UPS is supplying utility power
to connected equipment.
The Online LED illuminates
green.
None N/A
On Battery
The UPS is supplying battery power
from the internal battery pack.
The Online LED illuminates
amber.
The UPS beeps 4 times
every 30 seconds.
The beeping stops when utility
power is restored or the M
UTE
button is pressed for 2 seconds.
System Fault
The UPS detects an internal system
fault.
System Fault LED illuminates
red.
Constant tone The alarm stops when the
P
OWER
O
N
/O
FF
button is
pressed for 2 seconds to trigger a
Fault Reset.
Site Wiring Fault
The building wiring presents a shock
hazard that must be corrected by a
qualified electrical.
Site Wiring Fault LED flashes
red.
None N/A
Status LCD Icon Audible Alarms Audible Alarm Terminates
On Battery
The UPS is supplying battery power to the
connected equipment.
Beeps 4 times every 30
seconds.
The beeping stops when utility
power is restored or the UPS is
turned off.
Utility Power Overload
An overload condition has occurred while
the UPS is operating on utility power.
Constant tone The alarm stops when nonessential
equipment is disconnected from the
outlets or the UPS is turned off
Battery Power Overload
An overload condition has occurred while
the UPS is operating on battery power.
Constant tone The alarm stops when nonessential
equipment is disconnected from the
outlets or the UPS is turned off.
Low Battery
The UPS is supplying battery power to the
connected equipment and the battery is
near a total discharge state.
Continuous beeping The beeping stops when utility
power is restored or the UPS is
turned off.
Battery Fault
The UPS is operating on utility power, but
the battery is not functioning properly. The
battery has reached the end of its useful
life.
N/A Replace the battery.
System Fault
The UPS has experienced an internal fault.
N/A Identify the fault message on the
display and refer to “System
Faults” .
F01 Output Short Circuit
F02 Output Overload
F03 AVR Relay Weld
F04 Output Over Voltage
F05 Unit Over Temperature
F06 Inverter