Smart-UPS X 2000/2200/3000 Vac XL 120/208/230/240 VA Tower/Rack-Mount 4U
9
Configuration
UPS Settings
Start up Settings
Use the display interface to configure these settings at initial start up. The UPS will prompt for a response to each
setting, if no response is given, the default setting will be used.
Note: The UPS will not turn on until all of these settings have been configured.
Function Factory Default Options Description
Language English • English
•French
•German
• Spanish
• Italian
• Portuguese
Japanese
The language for the display interface.
Language options will vary by model and firmware version.
Output
Voltage
Low Voltage: 120 Vac • 100
•110
•120
•127
Set the output voltage while the UPS is in Standby mode.
High Voltage: 230 Vac • 200
•208
•220
•230
•240
Input Power
Quality
Good Good
•Fair
•Poor
Select the desired utility power input quality.
• Good: The UPS will go on battery power more often to
provide the cleanest power supply to the connected
equipment.
• Fair: The UPS will tolerate some voltage fluctuations.
Poor: The UPS will tolerate more voltage fluctuations and
will go on battery power less often.
If unsure of the local power quality, or the connected
equipment is sensitive to voltage fluctuations set the
sensitivity level to Good, using the Advanced menu.
Menu Type Standard Standard or
Advanced
The advanced menus include all parameters. The Standard
menus display a limited set of menus and options.
Date UPS manufacture date
+ 90 days
mm-yyyy Enter the current date.