990-3467A 02/2009Smart-UPS® RTUninterruptible Power SupplyStack/Rack-Mount 12USURT14000/18000 VA200 VacSURT15000/20000 VA208/240 VacEnglish
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 11Wiring SpecificationsWire gauges may vary. Adhere to national and loca
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 12Input wiring Wiring must be performed by a qualified electrician.Adher
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 13Input hardwiringInstall input wiring tray in UPSL1N/L2su0154asu0155aGr
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 14Output wiringWiring must be performed by a qualified electrician. Adhe
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 15Hardwire the load1. Remove appropriate circular knockout from output w
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 16Connect PDU to output wiring tray1. Remove the five screws securing th
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 17Start-UpConnect battery modulesConnect all eight battery modules. Fail
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 18OperationNormal operationDuring normal operation, the UPS double conve
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 19Display interface The four LEDs to the left of the LCD indicate the op
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 20Navigating menu screensNavigating sub menu screensUse UP/DOWN arrow ke
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 3IntroductionOverviewThe American Power Conversion (APC®) Smart-UPS® RT
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 21ConfigurationUPS configuration options can be adjusted through the dis
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 22Setup/Settings/AlarmsAlarm Thresholds/Load14 kVA14 kVA 2, 4, 6, 8, 10,
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 23Menu screens mapRefer to the Configuration table on the previous pages
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 24View LogClear LogView Statisticsxxx Transfers->Bat.xxx Transfers-&g
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 25LanguageContrastBeeper SetupDisplay SetupControlStatusSetupBatteriesLo
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 26Troubleshooting display messagesUse the table below to solve minor ins
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 27Threshold AlarmLoad Power Is Above Alarm Limit.The load has exceeded t
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 28General FaultShutdown Due To Low Battery.The UPS shutdown while on bat
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 29Maintenance and serviceReplace battery modulesThis UPS has easy-to-rep
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 30Two-Year WarrantyThe limited warranty provided by American Power Conve
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 4AccessoriesInstall accessories prior to connecting power to the UPS.Ref
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 31Contact informationAPC Worldwide Customer SupportCustomer support for
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 32
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 5Physical Specifications continuedFront and rear UPS panelsDimensionsUPS
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 6Stack and rack-mount installationBatteries must be removed from battery
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 7Install rails in rackFor details on rail installation refer to instruct
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 8Communication portsDisplay interface installationPrior to attaching the
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 9Route network cableNetwork cable wiring front panel accessThe NMC is in
SURT Stack/Rack-Mount 12U 14000/18000 VA 200 Vac 15000/20000 VA 208/240 Vac 10Emergency Power Off (EPO)The system power can be disabled in an emerge