APC SURT6000XLI Datasheet Page 4

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 3
2
Wiring and Connecting the UPS
5000/6000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS
Wiring must be performed by a qualified electrician.
Install a high magnetic 30/32 A utility circuit breaker.
Adhere to all national and local electrical codes.
Use #10 AWG gauge (5 mm
2
) wire.
1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.
4. Run #10 AWG gauge (5 mm
2
) wire through the access panel, and connect the wires to the
terminal block (green: ground, brown: hot, blue: neutral). Use an appropriate strain relief (not
included).
5. Switch the utility circuit breaker ON.
6. Check line voltages.
7. Replace the access panel.
Page view 3
1 2 3 4 5 6 7 8 9 ... 20 21

Comments to this Manuals

No comments