Installation
4 Smart-UPS RT SURTA1500XL/SURTA1500XLJ/SURTA2000XL Uninterruptible Power Supply User Manual
The EPO feature provides immediate de-energizing of the UPS and connected equipment from a
remote location, without switching to battery operation.
1. Use one of the following cable types to connect the UPS to the EPO switch.
CL2: Class 2 cable for general use.
CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.
CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.
CLEX: Limited use cable for use in dwellings and for use in raceways.
For installation in Canada: Use only CSA certified, type ELC (extra-low voltage control
cable).
For installation in other countries: Use standard low-voltage cable in accordance with national
and local regulations.
2. Locate the EPO connector on the rear of the UPS. Use a normally-open contact to connect
cable to each EPO terminal .
Connect the Battery and Install the Front Bezel
The battery is shipped in the disconnect position. Do not connect the battery until you are ready to use
the equipment.
1. Remove the battery cover .
2. Remove the warning label and protective sticker from the battery connector. Place the sticker on
the back of the battery cover for re-use.
3. Snap the battery connectors together .
4. Reinstall the battery cover .
5. Install the front bezel .