Troubleshooting
Symmetra
®
PX 10-80 kW, 208V – Operation & Maintenance Guide – 990-1430 REV01 25
General Fault
Display Message Meaning Corrective Action
Need Bat Replacement One or more battery
modules are in need of replacement
Refer to Module Replacement Section
for procedures.
The Redundant Intelli-
gence Module is in con-
trol
The Main Intelligence Module has
failed, and the redundant intelligence
module is functioning as the primary
intelligence module.
Replace the Main Intelligence Mod-
ule.Refer to Module Replacement
Section for procedures.
UPS Fault A fault has occurred in a power mod-
ule. This will always occur with a
power module failure message.
Contact APC Technical Support at (1)
(800) 800-4272.
On Battery The Symmetra PX UPS has trans-
ferred to battery operation due to the
input going out of acceptable range.
At this time the batteries will dis-
charge until the input is restored to an
acceptable range.
No corrective action necessary.
Note: Runtime is limited in duration.
Prepare to shut down the Symmetra
PX UPS and the load equipment or
restore incoming voltage.
Shutdown or unable to
transfer to batt due to
overload
The Symmetra PX UPS has shut
down because an overload occurred
and bypass is not available.
Option 1: Reduce the load to elimi-
nate overload.
Option 2: If possible, add power
modules to eliminate overload.
Option 3: Replace failed power mod-
ules to eliminate overload.
Load Shutdown from
Bypass. Input Freq/Volts
outside limits
The Symmetra PX UPS has trans-
ferred to battery operation because the
input is out of acceptable range.
Correct the input voltage problem.
Fault, Battery Charger
Failure
The battery charger in one or more of
the power modules failed
Refer to Module Replacement Section
for procedures.
Fault, Internal Temp
exceeded normal limits
The temperature of one or more bat-
tery units has exceeded system speci-
fications.
Ensure that the ambient temperature
meets the specifications of the system.
Input circuit breaker
tripped open
The input circuit breaker on the Sym-
metra PX UPS is open. Input voltage
is disconnected to the Symmetra PX
UPS.
Option 1: If this occurs with an over-
load condition, decrease the load and
reset the breaker.
Option 2: If no overload condition
exists, reset the breaker. If it trips
open again, contact APC Technical
Support at (1) (800) 800-4272.
System level fan failed A cooling fan in the Symmetra PX
UPS failed.
Contact APC Technical Support at (1)
(800) 800-4272.