APC AP9604 Datasheet Page 9

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 8
Power Considerations 5
Power Considerations
The power required for the operation of the card is normally
provided to the Triple Chassis by the UPS. There is a limit to
the amount of power available, and the total power required by
all the cards installed in the Triple Chassis must not exceed this
limit. If this limit is exceeded, it is likely that the management
product will cease to operate properly. The limits are:
Smart-UPS — 200 mA
Matrix-UPS — 200 mA
To determine the total amount of power required, add the
individual power requirements for each of the management
products to be installed in the Triple Chassis, as well as the
power requirements for the Triple Chassis itself. The power
requirements for each individual card can be obtained from the
documentation included with that card.
Optional power
adapter
In cases where the power requirements exceed 200 mA, APC’s
optional 24VDC (AP9505, not supplied) adapter may be used
to supplement the UPS power by providing an additional 400
mA. The power adapter is also required under the following
conditions:
Smart-UPS models:
Serial number prior to S9405
Serial number starting with the letter W
All Smart-UPS 250 models
Matrix-UPS models:
When remote turn-on of the UPS is required
The optional power adapter is used with
100/120 VAC power only. AP9505I is also
available for universal power input, but
requires a customer-supplied line cord.
If you need to obtain a power adapter, contact APC Customer
Service at a telephone number on the back cover.