Page view 17
Environmental
OperatingTemperature
0-40°C
StorageTemperaturewithbatteries
-15-40°C
StorageTemperaturewithoutbatteries
-30-70°C
OperatingRelativeHumidity0-95%,non-condensing
StorageRelativeHumidity0-95%,non-condensing
OperatingElevation0-1000m:100%load
1000–1500m:95%load
1500–2000m:91%load
2000–2500m:86%load
2500–3000m:82%load
StorageElevation
0-15000meters
Audiblenoiseat70%load1meterfromsurface
ofunit
10-20kV A380/400/415V
30-40kV A380/400/415V
42.3dBA
46.2dBA
Audiblenoiseat100%load1meterfrom
surfaceofunit
10-20kV A380/400/415V
30-40kV A380/400/415V
51.3dBA
55.0dBA
ProtectionClass
UptoIP51
ColourDarkgrey
HeatDissipation
3:3380V,400V,415V
10kV A15kV A20kV A30kV A40kV A
Batteries
Fully
charged
Charg-
ing
Fully
charged
Charg-
ing
Fully
charged
Charg-
ing
Fully
charged
Charg-
ing
Fully
charged
Charg-
ing
Heat
dissipation
(BTU/hr)
1474202019652784267533673439453152416333
3:1380V,400V,415V
15kV A20kV A30kV A40kV A
Batteries
Fully
charged
ChargingFully
charged
ChargingFully
charged
ChargingFully
charged
Charging
Heat
dissipation
(BTU/hr)
20882907289339854094518658966988
12
MGE™Galaxy™3500380/400/4153:310-40kV A3:115-40kV A