CommunicationandManagement
NetworkManagementCard
Thesystemisequippedwithonenetworkmanagementcardforremotemonitoringandcontrolofan
individualUPSbyconnectingitdirectlytothenetwork.
A
NetworkManagementCard
InputandOutputContacts
Pins7and8areforexternalchargecontrol.When7and8areclosed,theUPSchargesbatterieswitha
pre-denedpercentage(0-25-50-75-100%)ofthemaximumchargingpower.Tobeusedingenerator
applications,orifspecialcodesrequirecontrolofcharging.
Pins5and6areforexternalmaintenancebypassQ3(auxiliaryswitchN/Ctype).WhenQ3isclosed,
signalsarefedbacktotheUPScontroller.
Pins1to4areforbatterymeasurement(onlyapplicabletoAPCXRBatteryEnclosures).
990–3661A-001
MGE™Galaxy™3500380/400/4153:310-40kV A3:115-40kV A
33