APC PD40G6FK1-M Instruction Manual Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
3InfraStruXure Power Distribution Unit 40kW Instructions for Electricians
Torque specs and tools required
Before connecting to the terminals, verify the torque specs below by checking the specifications on the Main
Input switch.
Terminal Torque Tools
L1, L2, L3 150 in-lb 6-mm Allen wrench
N
125 in-lb 13-mm socket wrench
G, G EC 4 – 6 AW G : 45 i n -l b
8 AWG: 40 in-lb
Slotted screwdriver
Only on PDUs without a transformer.