Environmental
OperatingTemperature0-40°C(32-104ºF)
StorageTemperaturewithbatteries-15-45°C(-5-113ºF)
StorageTemperaturewithoutbatteries-30-70°C(-22-158ºF)
OperatingRelativeHumidity0-95%,non-condensing
StorageRelativeHumidity0-95%,non-condensing
OperatingElevation0-1000m(0-3000ft):100%load
1000-1500m(3000-4500ft):95%load
1500-2000m(4500-6000ft):91%load
2000-2500m(6000-8000ft):86%load
2500-3000m(8000-10000ft):82%load
StorageElevation0-15000m(0-50000ft)
Audiblenoiseat70%load1meterfromsurfaceofunit
10-15kV A208/220V
20-30kV A208/220V
42.3dBA
46.2dBA
Audiblenoiseat100%load1meterfromsurfaceofunit
10-20kV A208/220V
30kV A208/220V
51.3dBA
55.0dBA
ProtectionClass
?
ColourBlack
OnlineThermalDissipationkw(BTU/hr)10kV Abatteriesfullycharged:0.57(1938)
10kV Abatteriescharging:0.65(2211)
15kV Abatteriesfullycharged:0.88(2989)
15kV Abatteriescharging:0.99(3398)
20kV Abatteriesfullycharged:1.24(4238)
20kV Abatteriescharging:1.42(4852)
30kV Abatteryfullycharged:1.73(5896)
30kV Abatterycharging:1.97(6715)