CHAPTER 3: INSTALLATION
8
Wiring the Step-Down Transformer
1. For cord connected installations:
Plug the input power cord into the outlet receptacle.
2. For hardwired installations:
Verify that all branch circuit (mains)
are de-energized, and locked out
before installing cables or making
connections.
Wiring by a licensed electrician is
required.
Check national and local codes
before wiring.
Use 10-gauge (6 mm
2
) wire.
3. Make sure the input circuit breaker is OFF.
a. Remove the input-wiring access panel .
b. Disconnect the power cord from terminal block .
c. Connect the new wires to the terminal block.
d. Each terminal is labeled. The Step-Down
Transformer requires a 200 or 208 VAC single-
phase input from a power source with a minimum
branch breaker rating of 30 amps.
e. Inspect the connections.
f. Attach the new access panel provided in the
literature kit.