Page 1 - Symmetra MW UPS

Symmetra MW UPS800 kW400 VInstallationGuide

Page 2

4 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BConfigurationsThe UPS system can be configured in two ways. The Inverter Section can

Page 3 - Contents

System Overview: ConfigurationsSymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 5Configuration 2 (Inverter Section placed to the right)

Page 4

6 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BExternal Bypass Static SwitchThe External Bypass Static Switch (External Bypass SSW)

Page 5

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 7Electrical InstallationTypical UPS Wiring PrinciplePower wiring overviewSee alsoSee s

Page 6

Electrical Installation: Typical UPS Wiring Principle8 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BExternal disconnection switchesI

Page 7 - - SAVE THESE INSTRUCTIONS

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 9Top Cable EntryPreparing for top cable entry (Default)Cable entry in Top Cover of Inp

Page 8 - Installation safety

Electrical Installation: Top Cable Entry10 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BInstall cable lugs on busbars. Use M12 bolt

Page 9 - System Overview

Electrical Installation: Top Cable EntrySymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 11Feed the battery cables through the grommet

Page 10 - Configurations

Electrical Installation: Top Cable Entry12 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BPE and AC cable connections (top cable entry

Page 11

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 13Bottom Cable EntryPreparing for bottom cable entryCable entry in bottom cover of Inp

Page 13 - Electrical Installation

Electrical Installation: Bottom Cable Entry14 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BPreparation for bottom cable entrya. Loo

Page 14

Electrical Installation: Bottom Cable EntrySymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 15Battery cable connection (bottom cable en

Page 15 - Top Cable Entry

Electrical Installation: Bottom Cable Entry16 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BConnect cables from battery system.Conn

Page 16

Electrical Installation: Bottom Cable EntrySymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 17PE and AC cable connections (bottom cable

Page 17 - 44.45 mm

External Bypass Static Switch WiringWARNING!Before installation work is carried out, check and test that all AC and DC power source breakers are in op

Page 18 - Connect cables

Electrical Installation: External Bypass Static Switch WiringSymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 19Top cable entryLoosen

Page 19 - Bottom Cable Entry

Electrical Installation: External Bypass Static Switch Wiring20 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BBottom cable entryLoos

Page 20

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 21Communication cable overviewConnection plane0P0957X131X130ExternalEPOplaced onwallX1

Page 21

22 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BRelay Board (Optional)Location of optional Relay Board123123123123123123NC 3123 123

Page 22

Electrical Installation: Relay Board (Optional)Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 23Communication cables with optional Re

Page 23

ContentsSymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B iSafety ...

Page 24

Electrical Installation: Relay Board (Optional)24 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BRelay Board functionsThe Relay Board

Page 25 - Top cable entry

Electrical Installation: Relay Board (Optional)Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 25K11 Bypass operation • UPS is running

Page 27 - Battery CAN I/O board

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 27SpecificationsLow-Impedance/High-Impedance EarthingThe Symmetra® MW is easily integr

Page 28 - Relay Board (Optional)

28 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BElectrical SpecificationsAC InputWARNING!Supply the UPS from a dedicated, 3 × 400/23

Page 29 - Shunt trip

Specifications: Electrical SpecificationsSymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 29DC InputAC OutputAC Input External Bypass S

Page 30 - Relay Board functions

Specifications: Electrical Specifications30 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BNotes1. Nominal (Nom): Input current based

Page 31

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 31Required Breaker Settings (400 V Systems)The Symmetra® MW is a fault-tolerant system

Page 32

Specifications: Required Breaker Settings (400 V Systems)32 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B22 kA is the maximum peak l

Page 33 - Specifications

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 33Appendix System and Protective EarthingThe purpose of this appendix is to describe t

Page 34 - Electrical Specifications

ii Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BBottom Cable Entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 35 - Heat dissipation

34 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BTN SystemsCharacteristicsTN systems have one point connected directly to ground. All

Page 36 - Torque specifications

Appendix: TN SystemsSymmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 35Additional requirements for generating sets (IEC 60364-5-55 551.

Page 37 - See also

Appendix: TN Systems36 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BThe characteristics of protective devices and the circuit impeda

Page 38

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 37TT SystemsCharacteristicsTT systems have one point connected directly to ground and

Page 39 - Appendix

Appendix: TT Systems38 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BWhen the protective device is an overcurrent protective device,

Page 40 - TN Systems

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 39IT SystemsCharacteristicsIn IT systems the installation is insulated from earth or c

Page 41 - Appendix: TN Systems

Appendix: IT Systems40 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BIn installations where the neutral is distributed, the following

Page 42

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2Protective Earthing ConductorProtective

Page 43 - TT Systems

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2Protective Earthing ConductorProtective

Page 44 - Appendix: TT Systems

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2PEProtective Earthing Conducto rMain Pr

Page 45 - IT Systems

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B iiiTT Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 46

Mains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2Main Protective Earthing TerminalExternal SSW-BypassSymmetra

Page 47

Residual Current SenseMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2PEProtective Earthing ConductorMain Pro

Page 48

Residual Current Sens eMains - inputUPS - outputPENPEPEPEBypass - input Bypass - outputL1L3L2L1L3L2NL1L3L2L1L3L2( Alternative to earth electrode )Eart

Page 50

*990-1510B*APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following ways:• V

Page 52

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 1SafetyIMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONSThis guide contains impo

Page 53

Safety: IMPORTANT SAFETY INSTRUCTIONS - SAVE THESE INSTRUCTIONS2 Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510BInstallation safetyPre

Page 54 - *990-1510B*

Symmetra MW 800 kW 3 × 400/230 V Installation Guide - 990-1510B 3System OverviewUPS SectionsSerial numberThe serial number is stated on the type label