Smart-UPS® VT ISX w/transformer, 20-30 kVA, 480 V, Installation
Minimum breaker settings
Note 1: the short-circuit level is indicated for the output value.
Recommended phase-conductor sizes [AWG] for
a 86°F (30°C) temperature environment
20kVA
Internal
fault
800%
overload
bypass
operation
150%
overload
normal/
battery
operation
125%
overload
normal/
battery
operation
Conti-
nuously
Mains input 4kA 68A
Bypass input 2.3kA 444A 62A
Output 14kA 444A 84A 70A 62A
Duration <10ms 500ms 30 s 60 s
Notes 1
30kVA
Internal
fault
800%
overload
bypass
operation
150%
overload
normal/
battery
operation
125%
overload
normal/
battery
operation
Conti-
nuously
Mains input 5kA 102 A
Bypass input 4.2k A 444 A 92 A
Output 14k A 444 A 125 A 105 A 92 A
Duration <10 ms 500 ms 30 s 60 s
Notes 1
UPS/AWG
sizes
Mains
input [AWG]
AC
output [AWG]
DC input
[AWG], 75ºC Wire
20 kVA 6 4 4
30 kVA 4 1 1
Cable Size
[AWG]
Cable Lug
Type
Crimping
Tool
Die
Terminal
Bolt
Diameter
6 YA6CL2TC38 MD7-34R W5CVT 0.2 in/6 mm
4 YA4CL2TC38 MD7-34R W4CVT 0.2 in/6 mm
1 YA1CL2TC38 MD7-34R W1CVT 0.2 in/6 mm
6
Wiring Verification
Do not connect batteries in the UPS.
If an XR Enclosure is installed make sure that the DC breaker is in the
OFF position and that both 125A fuses are removed from the XR
Enclosure.
Check that the power wiring is torqued to 45 lbf
.
in/5 Nm.
If your installation includes an XR Enclosure, remount the 125A
fuses in the XR Enclosure and check that the DC breaker on the XR
Battery Enclosure is in the ON position.
Make sure the cable landing cover plates are installed.
Leave a wiring diagram on site for service personnel.
If a problem occurs, phone Customer Support at (1) (800) 800-4272
(US and Canada). Refer to Contact Information for contact numbers
in other countries.
For any optional equipment, refer to product-specific manuals.
7
Load Connection
At the rear, the UPS contains at least one Distribution Units (PDU). As
standard, one PDU is installed on the left side seen from the rear. In
addition, a second PDU may be installed on the right side. The PDU has 6
breaker sets. The top breaker set operates as a unit and protects any 3-
phased equipment that may be connected to the PDU. This breaker unit
(must be toggled) will switch ON/OFF all 3 phases when operated (may
supply several loads). Each of the 5 other breaker sets protects the 5
single-phased outlets (L1, L2, L3) beneath the actual breaker set. The top
breaker in each of these 5 single-phased outlets protects L1, the middle
breaker protects L2, and the bottom breaker protects L3.
Connecting the load to the PDUs
Note
Use Molex lug type or equivalent, and crimp to
manufacturers specifications.
Warnin
g
At 100% non-linear load (EN50091-3 standard), the
neutral shall be rated for 200% phase current.
Smart-UPS® VT ISX w/transformer, 20-30 kVA, 480 V, Installation
.
Note
Connect the load equipment evenly between the 3 phases to
avoid overloading one particular single phase. The total
output capacity of the PDU is approximately twice the
output capability of the UPS. This means that UPS would be
over-loaded if all PDU outlets were loaded to their rating.
Load status on the individual phases can be found through
the UPS display or through the web interface.
Note
Equipment connected to the 3-phased output may require
overcurrent protection with a lower rating than the 3-phased
output.
Note
For 3-phased output, the highest current may be in the
Neutral conductor at non-linear loads (up to 173%) and may
trip the breaker.
Note
The UPS can support a 3-phase load if that load is connected
to the 3-phase terminal in order to ensure correct connection/
disconnection of the load across all 3 phases simultaneously
Note
ONLY single-phased Phase to Neutral loads may be
connected to the five L21-20 outlets as per NEC05. The
outlets have individual breakers for each phase for
maximum availability.