11NetBotz Rack Monitor 450/550/570 Installation and Quick Configuration Manual
Initial Configuration
Note: Disregard the procedures in this section if you have an APC InfraStruxure Central
server as part of your system. See the documentation for your InfraStruxure device for more
information.
Overview
You must configure the following TCP/IP settings before the appliance can operate on a network:
IP address of the appliance
Subnet mask
Default gateway
Note: If a default gateway is unavailable, use the IP address of a computer that is
located on the same subnet as the appliance and that is usually running. The appliance
uses the default gateway to test the network when traffic is very light.
Obtain network settings using DHCP
By default, your appliance obtains its network settings using DHCP. When you connect the appliance to
your network and apply power to the unit, it automatically attempts to contact a DHCP server. The
appliance waits 30 seconds for a response. If the DHCP server is configured to provide a hostname, the
appliance requests either its configured hostname or ‘netbotzxxxxxx’ (where xxxxxx is the last 6 digits of
the MAC address of the appliance) as a hostname associated with the IP address granted by the DHCP
server. This enables you to use a Web browser to connect to the appliance using the address
http://netbotzxxxxxx without any additional configuration. The appliance also requests DNS server
addresses, a DNS domain, SMTP server addresses, and NTP server addresses from the DHCP server.