NetBotz Wireless Sensor Pod 180 Installation Guide
Disconnecting a Coordinator
When you disconnect the Coordinator from the host appliance, all of the
sensors on the wireless sensor network display as offline. When you reconnect
the same Coordinator, it must be manually deleted and reconfigured in the
Wireless Sensor Setup task in the Advanced View. The network will then
restart, and the sensors will begin reporting data.
If you want to connect a different pod to the host appliance to become the
Coordinator, you must FIRST remove the extended address of the previous
Coordinator from the commission list.
See “Configuring the Coordinator” on page 9.
Maintaining sensor history. If you right-click a disconnected Coordinator
in the Navigation pane in the Advanced View and select “Delete Pod”, all of the
Wireless Sensor Pods will be deleted, including any sensor history related to
those devices.
To maintain your sensor history, remove the Coordinator using the Wireless
Sensor Setup dialog.
Warning: If a Coordinator is removed from the host appliance
after being configured as a serial device, it MUST be manually
deleted using the Wireless Sensor Setup dialog. You will not be
able to configure a Coordinator if the entry is not deleted, even
if the original pod is reconnected.
Internal sensor listing
When a Coordinator is selected in the Navigation Pane in Advanced View, the
following internal sensors are listed in the Sensor Pane (along with any attached
external sensors):
Sensor Description
Temperature The internal temperature sensor reading.
Humidity The internal humidity sensor reading.
Dew Point The calculated dew point.