Page view 13
10 Environmental Monitoring Card
Specifications
Product
specifications
Item Specification
Electrical
Operating voltage 16 27 VDC
Operating current
draw
30 mA DC (exclusive of any attached
sensors)
Temperature accuracy
± 2° C (±3.6° F) from 0 to 40° C
(32 to 104° F)
Humidity accuracy
± 8% RH, 10 to 90% RH
at 25° C (77° F)
± 8% RH, 30 to 80 % RH
from 15 to 30° C (from 59 to 95° F)
Physical
Size (h × w × d)
3.8 cm × 10.2 × 10.2
(1.5 i × n4 × 4)
Weight 140 g (0.3 lb)
Shipping weight 320 g (0.7 lb)
Environmental
Elevation:
Operating:
Storage:
0 to 3000 m (0 to 10,000 ft)
0 to 15 000 m (0 to 50,000 ft)
Temperature:
Operating:
Storage:
0 to 40° C (32 to 104° F)
25 to 65° C (–13 to 149° F)
Probe operating
temperature
0 to 60° C (32 to 140° F)
Approvals
EMC verification
FCC Class A, DOC Class A, EN55022
Class A
Electromagnetic
immunity
EN55024 verified