Microprocessor Controller
APC InRow SC Technical Data Manual 6
Microprocessor Controller
Microprocessor Controller
The microprocessor controller is
standard on each system. The con-
troller provides precision control
for the demanding requirements of:
• Data centers
• Server rooms
• Wiring closets
• Switch rooms
• UPS rooms
Open Architecture
The NetworkAIR SC protocol is
open for integration with all build-
ing management systems.
Communication interface on the
system is MODBUS RS485.
Control Type
Controller utilizes proportional and
integral derivative (PID), a time
proven precision environmental
control method. The PID is non-
adjustable, and can not be customer
configured.
Control
The backlit, four-line by twenty
character display is password
configurable.
Functions
• Supply and Return Air
Temperatures
• Operational Mode Control
• Event Logging
•Alarms
• Fan Speed Adjustment
• Input/Output Module
Programming
• Refrigerant Discharge and
Suction Pressure
• Suction Line Temperature
Logging
The microprocessor displays the 30
most recent alarms. Each alarm log
contains a time/date stamp as well
as operating conditions at the time
of occurrence. The controller also
displays run time, in hours, for
major components (Air Filter, Con-
denser Fans, Evaporator Fans,
Compressor, Condensate Pump,
Fan Power Supplies).
Factory Default Set Points:
• Cool: 72.0°F (22.2°C)
• Deadband: 1.8°F (1.0°C)
• Supply Air InRow: 64.0°F (17.8°C)
• Supply Air RACS: 64.0°F (17.8°C)
• Supply Air Spot: 57.0°F (13.9°C)
Alarms
• Air Filter Clogged
• Air Filter Run Hours Violation
• Condensate Pump Full Fault
• Condenser Fan #n Fault
• Cooling Failure
• Persistent High Discharge/Low
Suction Pressure Alarm
• Rack Inlet High Temperature
Violation/Fault
• Suction Pressure Sensor/
Temperature Fault
• Supply Air High Temperature
Violation
• Upper Return/Supply Air
Sensor Fault
• Water Detection Fault
• Discharge Pressure Sensor
Fault
• Evaporator Fan #n Fault
• External Communication Fault
• Fan Power Supply Left/Right
Fault
• Filter Sensor Fault
• High Discharge Pressure
Alarm
• Internal Communication Fault
• Lower Return/Supply Air
Sensor Fault
• Low Suction Pressure Alarm
• On Standby: Input Contact
Fault
X
Critical Alarm LED
Y
Warning Alarm LED
Z
Check Log LED
[
Status LED
\
Liquid Crystal Display (LCD)
]
Up and Down Arrow Keys
^
ESC key
_
Enter key
`
Help key