CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
APC Smart-UPS RT
BID SPECIFICATIONS FOR
3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC
Uninterruptible Power Supply
PART 1 - GENERAL
1.1 SUMMARY
A. This specification describes the operation and functionality of a continuous duty, single-
phase, solid-state, static Uninterruptible Power System (UPS) hereafter referred to as
the UPS.
B. The UPS utilizes double conversion online topology designed to protect electronic
equipment by supplying reliable, network-grade power featuring extremely tight
voltage and frequency regulation. The UPS also features internal bypass and input
power factor correction.
C. The primary sections of the UPS are: input disconnect and filter stage, input PFC power
stage, energy storage stage (DC bus capacitor bank), output power stage (inverter),
bypass and a battery charger. The control of power module and fault detection logic is
microcontroller based. Input disconnect and filter stage contains input backfeed relay
(in models with a input wire plug), input filter, transient suppression, battery select
transfer relays. Input PFC power stage contains non-isolated power factor correcting
AC/DC converters. This converter is capable of full power operation in very wide input
voltage range
or from a nominal DC battery voltage. The energy storage stage is a split
DC bus capacitor handling seamless transitions from battery to line and vice versa as
well as the low and high frequency power stages ripple. The inverter stage operates
directly from the DC bus and produces an AC output voltage of
200/208/220/230/240VAC output. The output of UPS is either connected through a
bypass relay to the inverter or to the input filtered line. UPS contains a battery charger,
which operates from the DC bus
.
D. The UPS batteries are modular, hot-swappable, user-replaceable.
E. In addition, this specification describes the performance, functionality, and design of
the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery
Systems, and connectivity solutions.
F. The UPS and associated equipment shall operate in conjunction with a primary power
supply and an output distribution system to provide quality uninterrupted power for
mission critical, electronic equipment load.
G. All programming and miscellaneous components for a fully operational system as
described in this specification shall be available as part of the UPS.
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM
Page view 0
1 2 3 4 5 6 ... 12 13

Summary of Contents

Page 1 - APC Smart-UPS RT

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM APC Smart-UPS RT BID SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptibl

Page 2

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 3.2 SOFTWARE AND CONNECTIVITY A. Network Adaptor: APC SmartSlot Network Management Card shall allow

Page 3

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 7. TurboLinux v.7.0 and 8.0 8. Novell Netware 6.0 with Support Pack 1 9. Novell Netware 6.5 1

Page 4

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 1. Ensure proper system start-up. 2. Verify proper firmware control functions. 3. Verify proper f

Page 5

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM identification and operation, system controls and adju

Page 6

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM H. Configuration Specifics: The UPS is available in one of the following configurations: MODEL SKU

Page 7

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM A. Online: The input PFC power stage and the output power stage (inverter) shall operate in an on-lin

Page 8

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2.1 MECHANICAL DESIGN A. The UPS is contained in a rugged steel cabinet with two plastic front bezel

Page 9

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 3. Output frequency: 50/60 +/- 3Hz tracking or 50/60 +/- 0.1Hz tracking (user selectable); 4. AC o

Page 10

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM C. Input Current Limit: 1. The input converter shall control and limit the input current draw from

Page 11

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM condition is removed from the critical bus output of the system. Automatic transfers of load to bypass

Page 12

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 6. Self-diagnostics, self-test and proactive fault detection; 7. Communication to the host server

Page 13 - End Of Section 16611

CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 6. The UPS is in fault state; 7. The battery needs to be replaced; 8. The battery capacity/utili