CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM APC Smart-UPS RT BID SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptibl
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 3.2 SOFTWARE AND CONNECTIVITY A. Network Adaptor: APC SmartSlot Network Management Card shall allow
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 7. TurboLinux v.7.0 and 8.0 8. Novell Netware 6.0 with Support Pack 1 9. Novell Netware 6.5 1
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 1. Ensure proper system start-up. 2. Verify proper firmware control functions. 3. Verify proper f
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM identification and operation, system controls and adju
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM H. Configuration Specifics: The UPS is available in one of the following configurations: MODEL SKU
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM A. Online: The input PFC power stage and the output power stage (inverter) shall operate in an on-lin
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 2.1 MECHANICAL DESIGN A. The UPS is contained in a rugged steel cabinet with two plastic front bezel
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 3. Output frequency: 50/60 +/- 3Hz tracking or 50/60 +/- 0.1Hz tracking (user selectable); 4. AC o
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM C. Input Current Limit: 1. The input converter shall control and limit the input current draw from
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM condition is removed from the critical bus output of the system. Automatic transfers of load to bypass
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 6. Self-diagnostics, self-test and proactive fault detection; 7. Communication to the host server
CSI SECTION 16611 STATIC UNINTERRUPTIBLE SYSTEM 6. The UPS is in fault state; 7. The battery needs to be replaced; 8. The battery capacity/utili