Magnum VS 50 Magnum VS 100 -48 Vdc Power Systems User’s Manual
Magnum VS –48 Vdc User’s Manual Page 5 Ventilation The rectifier modules for this system have fans that prov
Magnum VS –48 Vdc User’s Manual Page 6 Rectifier Terminal # Function Terminal # Function Terminal # Function
Magnum VS –48 Vdc User’s Manual Page 7 3.4. Battery Connections WARNING: Hazardous energy levels are pr
Magnum VS –48 Vdc User’s Manual Page 8 Figure 3.4-1 Battery Cable Connection Locations Battery Temperature
Magnum VS –48 Vdc User’s Manual Page 9 3.5. Counter Electro-Motive Force (CEMF) Cell Connections WARNING:
Magnum VS –48 Vdc User’s Manual Page 10 3.7. Load Protection Installation Circuit Breaker Installation Sta
Magnum VS –48 Vdc User’s Manual Page 11 3.8. Load Connections Cable Size Considerations The dc load cable
Magnum VS –48 Vdc User’s Manual Page 12 Figure 3.8-2 Top Shelf GMT Fuse Connections Figure 3.8-3 Bottom Sh
Magnum VS –48 Vdc User’s Manual Page 13 Figure 3.9-3 shows the alarm output connection designations. Wheneve
Magnum VS –48 Vdc User’s Manual Page 14 OUT RELAY #6 N/A NO N/A MINOR C N/A NC N/A NO N/A
Magnum VS –48 Vdc User’s Manual Page ii Table of Contents 1 Safety First!...
Magnum VS –48 Vdc User’s Manual Page 15 2) Slide the rectifier module into the shelf between the guides unti
Magnum VS –48 Vdc User’s Manual Page 16 4 Commissioning This section is intended as a guide when powering up a system for the first time. It may
Magnum VS –48 Vdc User’s Manual Page 17 8. Check that anti-oxidation compound is properly applied. 9. Visua
Magnum VS –48 Vdc User’s Manual Page 18 Rectifier Test: 1. To verify that all rectifiers are reporting corr
Magnum VS –48 Vdc User’s Manual Page 19 Output Relay 1: 1. Minor and Major output relays were tested in the
Magnum VS –48 Vdc User’s Manual Page 20 5 Technical Description The Power System is designed to supply safe –54 Vdc primary power through the use
Magnum VS –48 Vdc User’s Manual Page 21 System Current Monitor The controller monitors individual rectifier
Magnum VS –48 Vdc User’s Manual Page 22 GMT Fuses When a GMT fuse trips, a fuse element burns out allowing t
Magnum VS –48 Vdc User’s Manual Page 23 Battery Equalization Battery equalization equalizes the specific gra
Magnum VS –48 Vdc User’s Manual Page 24 Battery Low Voltage Disconnect In order to prevent damage to the bat
Magnum VS –48 Vdc User’s Manual Page iii AC Power Up...
Magnum VS –48 Vdc User’s Manual Page 25 5.5. Controls and Indicators Controller with Display The Magnum VS
Magnum VS –48 Vdc User’s Manual Page 26 network management card. This can be used to give specific informati
Magnum VS –48 Vdc User’s Manual Page 27 6 Operation 6.1. Description The Magnum VS is designed for years of operation with no user input. The po
Magnum VS –48 Vdc User’s Manual Page 28 J111110 165J5J3J13J9 J8J2J12J4DB9 - RS232 PortMAJORDC GOODMINOROUT RL
Magnum VS –48 Vdc User’s Manual Page 29 If the keypad is not pressed for approximately 2 minutes the display
Magnum VS –48 Vdc User’s Manual Page 30 Figure 6.4-1 Parameter Locations, Descriptions, and Default Values PA
Magnum VS –48 Vdc User’s Manual Page 31 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default Setting
Magnum VS –48 Vdc User’s Manual Page 32 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default Setting
Magnum VS –48 Vdc User’s Manual Page 33 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default Setting
Magnum VS –48 Vdc User’s Manual Page 34 Figure 6.4-2 Magnum VS English Display TreeENGLISH SETUP STATUS ALARMSENTER PIN 2 2 2 2 SYSTE
Magnum VS –48 Vdc User’s Manual Page iv 6.5. CONTROLLER WITHOUT DISPLAY...
Magnum VS –48 Vdc User’s Manual Page 35 Figure 6.4-3 Magnum VS Chinese Display Tree设置 状态 告警 PIN码输入 2 2 2 2 系统 电池 模块 系统 电池 PIN码设置
Magnum VS –48 Vdc User’s Manual Page 36 6.5. Controller without Display This controller does not have a built in display and keypad. It does not
Magnum VS –48 Vdc User’s Manual Page 37 6.7. Operation Using the 10/100 BaseT Ethernet Port The RJ-45 10/1
Magnum VS –48 Vdc User’s Manual Page 38 Figure 6.8-1 Parameter Locations, Descriptions, and Settings PARAMETE
Magnum VS –48 Vdc User’s Manual Page 39 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default setting
Magnum VS –48 Vdc User’s Manual Page 40 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default setting
Magnum VS –48 Vdc User’s Manual Page 41 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default setting
Magnum VS –48 Vdc User’s Manual Page 42 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default setting
Magnum VS –48 Vdc User’s Manual Page 43 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default setting
Magnum VS –48 Vdc User’s Manual Page 44 PARAMETER NAME/ [MENU LOCATION] DESCRIPTION SETTINGS (Default setting
Magnum VS –48 Vdc User’s Manual Page v Revision History Document # & Rev Date By Description 990-1479
Magnum VS –48 Vdc User’s Manual Page 45 the system and the bus voltage reaches the level defined by the LVD 1
Magnum VS –48 Vdc User’s Manual Page 46 information on the exact nature of the active alarm. Using the examp
Magnum VS –48 Vdc User’s Manual Page 47 7 Preventive Maintenance Preventive Maintenance is typically performed on a quarterly basis. 7.1. Equip
Magnum VS –48 Vdc User’s Manual Page 48 c) Interrupting Current Rating Battery Visual and Safety Inspection
Magnum VS –48 Vdc User’s Manual Page 49 3. Remove the second rectifier and verify that you get a Major alarm
Magnum VS –48 Vdc User’s Manual Page 50 Battery Preventive Maintenance Procedure The purpose of the preventi
Magnum VS –48 Vdc User’s Manual Page 51 8 Alarm Summary ALARM/ [MENU LOCATION] DESCRIPTION DEFAULT SETTINGS Battery Discharge Alarm [Batteries/Par
Magnum VS –48 Vdc User’s Manual Page 52 ALARM/ [MENU LOCATION] DESCRIPTION DEFAULT SETTINGS System LT Alm [Sy
Magnum VS –48 Vdc User’s Manual Page 53 9 Specifications The overall system specifications can vary, depending upon the number of rectifier module
Magnum VS –48 Vdc User’s Manual Page 54 Magnum VS 100 Power System Input Voltage Range 85 – 264 Vac AC Freq
Magnum VS –48 Vdc User’s Manual Page 1 1 Safety First! It is very important to follow all safety procedures when unpacking, installing and operati
Magnum VS –48 Vdc User’s Manual Page 55 Magnum VS 50 Power System Output Voltage (factory programmed) 54.0 V
Magnum VS –48 Vdc User’s Manual Page 56 9.3. Controls and Indicators TWF0500H54B Rectifier Input Healthy L
Magnum VS –48 Vdc User’s Manual Page 57 Dimensions 5-1/4 in (13.3 cm) high x 17-1/4 in (43.8 cm) wide x 13 i
Magnum VS –48 Vdc User’s Manual Page 58 9.6. Compliance NEBS Level 3 (Pending) Safety UL 60950 CE Marked t
Magnum VS –48 Vdc User’s Manual Page 59 10 APC Worldwide Customer Support Customer Support for this or any other APC product is available at no
Magnum VS –48 Vdc User’s Manual Page 60 11 Limited Product Warranty The limited warranty provided by American Power Conversion Corporation ("
Magnum VS –48 Vdc User’s Manual Page 2 2 Introduction 2.1. General Information DC Power Plants from APC hav
Magnum VS –48 Vdc User’s Manual Page 3 ACDCControlACDCControlACDCControlACDCControlACDCControlGNDL1 L2/NGNDL1
Magnum VS –48 Vdc User’s Manual Page 4 3 Installation 3.1. Unpacking Equipment Remove equipment from packing material and inspect for shipping da