APC Monitor 78-10169-02 Troubleshooting Guide Page 27

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 26
2-27
Cisco ICS 7750 Administration and Troubleshooting Guide
78-10169-02 Rev. B0
Chapter 2 Monitoring the System
Monitoring a UPS
Step 5 Verify that the Cisco ICS 7750 can communicate with the UPS:
fmmcli getchassisinfo | more
Information similar to the following will be displayed:
UPS status = AC
Battery Level = <non-zero value>
Batt. Span = <non-zero value>
Note If UPS status = UpsNotAvailable is displayed, verify that
your system components are properly connected and powered on.
Then try this procedure again.
Step 6 Unplug the UPS power cord.
The UPS emits an audio tone, and the ALARM LED on the SAP turns on (amber).
Step 7 Using the Telnet session that you opened at Step 2, enter the following command
to verify that the system has detected the change in power status:
fmmcli getchassisinfo | more
Information similar to the following will be displayed:
UPS status = DC
Battery Level = <non-zero value>
Batt. Span = <non-zero value>
Step 8 Open an ICS System Manager session (see Accessing ICS System Manager” on
page 1-9).
Step 9 Click the Event Manager tab on the ICS System Manager home page.
Step 10 At the bottom of the Live Viewer page, click Start Events.
Information similar to the following will be displayed:
AC power is off, using DC
Page view 26
1 2 ... 22 23 24 25 26 27 28

Comments to this Manuals