APC Smart-UPS RC 96V Battery Pack User Manual Page 3

  • Download
  • Add to my manuals
  • Print
  • Page
    / 15
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 2
SRC96XLBP / SRC96XLBP2S User Manual 4
Specifications
Environmental Specifications
Physical Specifications
Temperature
Operating 0° to 40° C (32° to 104° F) This unit is intended for indoor use
only. Select a location sturdy
enough to handle the weight.
Do not operate unit where there is
excessive dust or temperature or
humidity are outside specified
limits.
Environmental factors impact
battery life. High temperatures, poor
utility power, and frequent, short
duration discharges will shorten
battery life.
Storage -15° to 30° C (5° to 86° F)
charge UPS battery every six months
30° to 70° C (86° to 158° F)
charge UPS battery every three months
Maximum
Elevation
Operating 3,000 m (10,000 ft)
Storage 15,000 m (50,000 ft)
Humidity
0 to 95% relative humidity,
non-condensing
Weight - Refer to Safety Guide supplied with this unit for lifting guidelines.
XLBP
model
SRC96XLBP2S
without batteries
with two 48 V battery modules
15 kg (32 lbs)
35 kg (76 lbs)
SRC96XLBP
without batteries
with six 48 V battery modules
15 kg (32 lbs)
75 kg (164 lbs)
each 48 V battery module 10 kg (22 lbs)
Each 96 V battery string consists of two
48 V battery modules.
Maximum number of external battery packs
(XLBPs) supported by Smart-UPS RC
10
Combined weights of UPS and all XLBPs installed in a
rack must not exceed rack weight limits.
Dimensions
Length x Width x Height: 48 cm (19 in) x 43 cm (17 in) x 18 cm (7 in)
su0265a
Page view 2